Rating | 150 deg C, 30 Vac, Cable flame, Optional - Oil Resistant 80 deg C. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. Optional Fillers may be employed. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or thermoplastic-tape wrap. Such a barrier would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors. The designations of all styles of individual conductors used in making up the cable assembly shall be available. |
|
Shield | Optional. |
|
Jacket | Extruded FEP |
| dia of cable under jacket |
| 0.425 inch or less | 25 mils min average | 20 mils minimum at any point |
| 0.426-0.700 dia | 30 avg | 24 min |
| 0.701-1.500 dia | 45 avg | 36 min |
| 1.501-2.500 dia | 60 avg | 48 min |
| 2.501 dia and larger | 80 avg | 64 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection or internal wiring of appliances or electronic equipment. In addition, the tag may also indicate the following: Suitable for immersion in oil at 80 deg C. |
|