APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2129 Issued:1959-05-01
Revised:2019-11-06
Style 2129 Multi-conductor cable using Extruded Non-integral Jacket.

Rating60, 80, 90, or 105 deg C; 600 or 1000 Vac, Horizontal flame.
Conductor28 AWG - 9 AWG solid or stranded round.
InsulationExtruded PVC, 30 mils min average, 27 mils minimum at any point or Labled or complying with Manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs or groups of twisted singles twisted together, or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldOptional
JacketExtruded PVC
Dia. of cable under jacket in inches
0.700 or less*30 mils min average24 mils minimum at any point
0.701-1.000 dia45 avg36 min
1.001-1.500 dia60 avg48 min
1.501-4.500 dia80 avg64 min
*Major diameter if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024