APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2748 Issued:1975-09-04
Revised:2019-11-06
Style 2748 Multiple-conductor cable using non-integral jacket.

Rating150 deg C, 600 Vac, Horizontal flame, Oil Resistant 80 deg C (optional).
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or thermoplastic-tape wrap. Such a barrier would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
ShieldOptional.
JacketExtruded FEP;
cable dia in inches
0.425 or less20 mils minimum average thickness18 mils minimum thickness at any point
0.426-0.700 dia30 avg26 min
0.701-1.500 dia45 avg40 min
1.501-2.500 dia60 avg. 55 min
2.501 dia and larger90 avg82 min.
- Major dia if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring. The tag may also indicate 2500 volts peak - For Electronic Use Only.