			| Rating | 150 deg C, 600 Vac, Horizontal flame. | 
			|  | 
			| Conductor | 0.5 - 250 sq mm, solid or stranded. | 
			|  | 
			| Insulation | Extruded Silicone rubber | 
			|  | Conductor size (sq mm) | mils min average | mils min at any point | 
			|  | 0.5-4.0 | 30 | 27 | 
			|  | 4.1-9.0 | 45 | 40 | 
			|  | 9.1-35.0 | 60 | 54 | 
			|  | 35.1-100.0 | 80 | 76 | 
			|  | 100.1-250.0 | 95 | 85 | 
			|  | May be applied in two layers with an intermediate glass braid (optional). | 
			|  | 
			| Standard | Appliance Wiring Material UL 758. | 
			|  | 
			| Marking | General. | 
			|  | 
			| Use | Internal Wiring of Appliances where totally enclosed. | 
			|  |