| Rating | 180 deg C, 7200 Vac, Horizontal flame. |
|
| Conductor | 16 AWG - 800 kcmil, solid or stranded. |
|
| Insulation | Extruded SR. |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 16 - 4 AWG | 90 mils | 81 mils |
| 3 AWG - 450 kcmil | 105 mils | 95 mils |
| 500 - 800 kcmil | 135 mils | 121 mils |
|
| Covering | Optional - Non-Metallic |
|
| Braid | Optional. |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | Internal wiring. |
|