Rating | 150 deg C, 600 Vac, Horizontal flame. |
|
Conductor | 30 AWG - 4 AWG solid or stranded round, tinned or bare copper. |
|
Insulation | XLPE. |
| conductor size | min average | minimum at any point |
| 30-9 AWG | 30 mils | 27 mils |
| 8-4 AWG | 45 avg | 40 min |
| or labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Two to six conductors, fillers and/or barrier tapes optional. |
|
Jacket | XLPE |
| dia of cable under jacket | min average | minimum at any point |
| 0-0.500 inches | 30 mils | 24 mils |
| 0.501-0.750 dia | 45 mils | 36 mils |
| 0.751-1.000 dia | 60 mils | 48 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Special use power supply cords or external interconnection used in high temperature equipment such as appliances, electronics and lighting equipment where the acceptability of the combination will be determined by Underwriters Laboratories. |
|