Rating | 80, 90, or 105 deg C, 600 Vac, FT2 flame. |
|
Insulated Conductor | 30 AWG - 750 kcmil, solid or stranded. Labeled or complying with the manufacturer's AWM procedure. Extruded PVC insulation. |
| Conductor size | Minimum average insulation thickness | Minimum insulation thickness at any point |
| 30-16 AWG | 20 mils | 18 mils |
| 14-10 AWG | 32 mils | 28 mils |
| 8-4 AWG | 46 mils | 40 mils |
| 2-3/0 AWG | 56 mils | 50 mils |
| 4/0 AWG-300 kcmil | 70 mils | 62 mils |
| 350-500 kcmil | 86 mils | 76 mils |
| 500-750 kcmil | 110 mils | 99 mils |
|
Shield | Optional. |
|
Jacket | Extruded PVC. |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.425 inch or less | 45 mils | 36 mils |
| 0.426-0.700 inch | 60 mils | 48 mils |
| 0.701-1.500 inch | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection of electronic equipment. |
|