APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10198 Issued:1994-02-10
Revised:2014-07-02
Style 10198 Single Conductor with Extruded Insulation

Rating105 deg C, 300 Vac, Horizontal flame.
Conductor30 AWG - 4/0 AWG, solid or stranded or braided.
InsulationExtruded PVC.
Conductor sizeMinimum average thicknessMinimum thickness at any point
30-16 AWG15 mils13 mils
15-9 AWG20 mils17 mils
8-2 AWG30 mils27 mils
1-1/0 AWG40 mils36 mils
2/0-4/0 AWG50 mils45 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseGround strap lead wire for the internal wiring of electronic equipment where the acceptability of the combination is to be determined by Underwriters Laboratories Inc.

UL and the UL Logo are trademarks of UL LLC © 2024