APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10200 Issued:1994-02-10
Revised:2013-12-18
Style 10200 Single Conductor with Extruded Insulation with an Extruded Non-integral Jacket.

Rating105 deg C, 600 Vac, Horizontal flame.
Conductor26 AWG - 1000 kcmil solid or stranded round, tinned or bare copper.
InsulationExtruded TPE 26-12 AWG conductor size, 15 mils min average, 13 mils minimum at any point; 11-10 AWG, 20 avg, 18 min; 9-5 AWG, 30 avg, 27 min; 4-2 AWG, 40 avg, 36 min; 1-4/0 AWG, 50 avg, 45 min; 213-500 kcmil, 60 avg, 54 min; 501-1000 kcmil, 70 avg, 63 min.
CoveringExtruded POLYAMIDE,26-10 AWG,4 mils min; 11-10 AWG, 4 mils min; 9-5 AWG, 5 min; 4-2 AWG, 6 min; 1-4/0 AWG, 7 min; 213-500 kcmil, 8 min; 501-1000 kcmil, 9 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024