APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10315 Issued:1997-09-10
Revised:2012-01-11
Style 10315 Insulated Wire.

Rating125 deg C, 300 Vac, Horizontal flame.
Conductor40 AWG - 6 AWG solid or stranded, solid magnet, litz cable magnet wire or R/C (OBMW2) magnet wire with AWG size to be determined by the Resistance Test. And tinned copper.
InsulationExtruded ETFE
Conductor sizeMinimum average thicknessMinimum thickness at any point
40-20 AWG5.5 mils5 mils
19-15 AWG8 mils7 mils
14-10 AWG13 mils12 mils
9-6 AWG20 mils18 mils
May be in two or three layers.
AssemblyEach single magnet wire strand is cabled together with other magnet wire strands to form a conductor.
StandardAppliance Wiring Material UL 758.
MarkingGeneral. Optional - Tags may indicate the following: "600 Volts peak for electronic use only".
UseInternal wiring of electronic equipment, such as electronic computers and business machines, where not subject to movement or mechanical damage. May also be used for further processing in cables and lead wire for UL 1950 applications.