Rating | 105 deg C, 300 Vac, Cable flame. |
|
Conductor | 40 AWG minimum. solid or stranded. |
|
Insulation | Labeled or complying with Manufacturer's AWM Procedure. |
|
Covering | Optional. Extruded PVC, 6 mils or heavier thickness, may be extruded over the conductor assembly. |
|
Shield | Optional. |
|
Jacket | Extruded PVC |
| Diameter of core assembly under jacket* | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 60 mils | 48 mils |
| 1.001-1.501 inch | 80 mils | 64 mils |
| * - Major diameter if cable is flat or oval. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or extrunal wire. Tags may also indicate the following: "600 Volts peak for Electronic Use Only." |
|