APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10404 Issued:1999-01-26
Revised:2012-04-26
Style 10404 Multiple-conductor cable using non-integral jacket

Rating60 deg C, 30 Vac, Horizontal flame.
InsulationLabeled or complying with Manufacturer's AWM Procedure.
CoveringOptional. A 6 mils or heavier covering of PE, PTFE, PVC, PFA, FEP or ETFE may be extruded over the conductor assembly or groups of singles.
ShieldOptional.
JacketExtruded PVC, 15 mils min average, 12 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring in Class 2 circuits of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2025