APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1042 Issued:1959-05-01
Revised:2011-07-28
Style 1042 Insulated Wire.

Rating60 deg C, 300 Vac, Horizontal flame.
Conductor20 AWG - 16 AWG Solid or Stranded Round, tinned or bare copper. No. 18-16 AWG. shall be stranded. All stranded conductors shall consist of No. 30 AWG. or smaller strands.
InsulationPVC, 30 mils min average, 27 mils minimum at any point.
CoveringExtruded nylon in 2-mil minimum thickness.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring of Lighting Circuits in Refrigerating Equipment.
 
UL and the UL Logo are trademarks of UL LLC © 2024