Rating | 90 or 105 deg C, 600 Vac. |
|
Conductor | 30 AWG - 1000 kcmil, solid or stranded. |
|
Insulation | Extruded PVC |
| 30-12 AWG conductor size | 15 mils min average | 13 mils minimum at any point |
| 11-10 AWG | 20 avg | 18 min |
| 9-5 AWG | 30 avg | 27 min |
| 4-2 AWG | 39 avg | 35 min |
| 1-4/0 AWG | 47 avg | 42 min |
| 213-500 kcmil | 60 avg | 54 min |
| 501-1000 kcmil | 70 avg | 63 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For further processing into cables only. |
|