|
Rating | 80 deg C, 600, or 1000 Vac. |
|
Conductor | 32 AWG - 2000 kcmil solid or stranded. |
|
Insulation | PUR |
| 32-20 AWG conductor size | 12 mils min average | 10 mils minimum at any point |
| 19-16 AWG | 14 avg | 12 min |
| 15-10 AWG | 16 avg | 14 min |
| 9-6 AWG | 22 avg | 19 min |
| 5-2 AWG | 28 avg | 25 min |
| 1-1/0 AWG | 33 avg | 30 min |
| 250-500 kcmil | 45 avg | 40 min |
| 501-1000 kcmil | 60 avg | 54 min |
| 1001-2000 kcmil | 80 avg | 72 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For further processing into Cables only. |
|