APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10528 Issued:2000-12-29
Revised:2012-06-19
Style 10528 Single Conductor with Extruded Insulation

Rating75 deg C, 600, 1000 Vac, Horizontal flame.
Conductor50 AWG - 2000 kcmil solid or stranded round.
InsulationFRPE or PE
50-10 AWG conductor size30 mils min average27 mils min at any point
9-8 AWG45 avg41 min
7-2 AWG60 avg54 min
1-4/0 AWG80 avg72 min
250-500 kcmil95 avg86 min
501-1000 kcmil 110 avg99 min
1001-2000 kcmil 125 avg112 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal.

UL and the UL Logo are trademarks of UL LLC © 2024