APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10572 Issued:2001-07-17
Revised:2012-01-18
Style 10572 Single insulation with extruded Non-integral Jacket

Rating105 deg C, 1000 Vac, Horizontal flame, Cable flame.
Conductor30 AWG minimum, solid or stranded round.
InsulationSingle conductor, Labeled or complies with Manufacturer's AWM Procedure.
CoveringOptional.
ShieldOptional.
JacketExtruded PVC
dia of core assembly under jacket in inchesMinimum average thicknessMinimum thickness at any point
0.425 or less30 mils24 mils
0.426-0.70045 mils36 mils
0.701-1.00060 mils48 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal wiring