APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10581 Issued:2001-08-23
Revised:2012-04-17
Style 10581 Single conductor with extruded or non-extruded insulation

Rating200 deg C, 600 Vac, Horizontal flame.
Conductor36 AWG - 4/0 AWG, solid or stranded.
InsulationExtruded or tape wrapped PTFE
Conductor size (AWG)Minimum average thickness (mils)Minimum thickness any point (mils)
36 - 10109
8 - 21513
1 - 4/02018
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024