APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10682 Issued:2003-05-28
Revised:2011-08-04
Style 10682 Single Conductor with Extruded Non-Integral Jacket

Rating105 deg C, 600 Vac, Cable flame
Conductor32 AWG minimum solid or stranded
InsulationLabeled or complying with manufacturer's AWM procedure
ShieldOptional
CoveringOptional
JacketExtruded PVC
@Diameter of coire assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
@ Major diameter if cable is flat or oval
StandardAppliance Wiring Material UL 758.
MarkingGeneral
UseExternal wiring

UL and the UL Logo are trademarks of UL LLC © 2024