APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10686 Issued:2003-05-28
Revised:2011-09-20
Style 10686 Single Conductor, PVC Jacket

Rating90 deg C, 1000 Vac Horizontal flame.
Conductor32 AWG minimum. Solid or stranded.
InsulationLabeled or complying with manufacturer's AWM procedure.
ShieldOptional.
CoveringOptional.
JacketPVC
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024