Rating | 80 deg C, 600 Vac |
|
Conductor | 19 AWG - 4/0 AWG solid or stranded round. |
|
Insulation | Extruded TPE |
| 19-12 AWG conductor size | 15 mils min average | 13 mils minimum at any point |
| 11-10 AWG | 20 avg | 18 min |
| 9-5 AWG | 30 avg | 27 min |
| 4-2 AWG | 40 avg | 36 min |
| 1-4/0 AWG | 50 avg | 45 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For further processing in cables. |
|