Rating | 105 deg C, 600 Vac. |
|
Conductor | Copper, 30 AWG - 1000 kcmil, solid or stranded, tinned or bare. |
|
Insulation | PVC. |
| Conductor size (AWG) | Minimum average thickness (mils) | Minimum thickness at any point |
| 30-12 | 15 | 13 |
| 11-10 | 20 | 18 |
| 9-5 | 30 | 27 |
| 4-2 | 39 | 35 |
| 1-4/0 | 47 | 42 |
| 213-500 kcmil | 60 | 54 |
| 501-1000 kcmil | 70 | 63 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | For further processing into cables only. Not for normal handling. |
|