APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10729 Issued:2003-09-26
Revised:2019-11-07
Style 10729 Single conductor cable using extruded non-integral jacket

Rating80 deg C, 30 Vac, Horizontal flame.
Conductor36 AWG - 2000 kcmil, solid or stranded.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyOne insulated conductor to form a round or flat cable. Assembly Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid, paper, nylon, oriented polyethylene terephthalate; thermoplastic covering, thermoplastic-tape wrap.
ShieldOptional.
CoveringOptional, extruded PVC or other thermoplastic covering may be extruded over the conductor assembly (with or without shields), 4 mil minimum average thickness.
JacketExtruded TPU
major dia in inches
0.350 or less15 mils min average12 mils min at any point
0.351-0.700 dia3024
0.701-1.000 dia4036
1.101-1.500 dia5448
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024