APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10747 Issued:2003-11-13
Revised:2019-11-07
Style 10747 Single-conductor cable using non-integral jacket.

Rating80 deg C, 300 Vac, Horizontal flame.
InsulationLabeled or complying with manufacturer's AWM Procedure having a minimum rating of 80C, 300Vac.
CoveringOptional.
ShieldOptional.
JacketPVC
dia in inches
0.700 or less30 mils min average24 mils minimum at any point
0.701-1.000 dia45 avg36 min
1.001-1.500 dia60 avg48 min
1.501-2.500 dia80 avg64 min
2.501-4.000 dia110 avg88 min
4.001 dia and larger140 avg112 min
BraidOptional.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024