APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10805 Issued:2003-11-28
Revised:2011-10-30
Style 10805 Multiconductor Cable with Extruded Non-Integral Jacket.

Rating80 deg C, 600 Vac, Horizontal flame, Cable flame.
InsulationLabeled or complying with manufacturer's AWM Procedure. Singles must be rated minimum 80ºC and 600 V.
CoveringOptional.
ShieldOptional.
JacketExtruded FRPE.
THICKNESS OF PVC JACKET (mils)
Dia. of Cable Under Jacket in Inches, Minimum Average, Minimum at any point; 0.700 or less, 30, 24; 0.701 - 1.000, 45, 36; 1.001 - 1.500, 60, 48; 1.501 - 2.500, 80, 64## Equivalent diameter of flat assembly = 1.1284 x (TW)0.5, where T is the thickness of the assembly under jacket, and W is the width of the assembly under jacket.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring and external interconnection of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024