APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10840 Issued:2004-03-01
Revised:2019-11-07
Style 10840 Single conductor cable with Extruded non-integral Jacket

Rating60 deg C, 150 Vac, Horizontal flame, Cable flame.
InsulationLabeled or complying with manufacturer's AWM Procedure
CoveringOptional.
ShieldOptional.
JacketPUR
dia in inches
0.700 or less30 mils min average24 mils minimum at any point
0.701-1.000 dia45 avg36 min
1.001-1.500 dia60 avg48 min
1.501-2.500 dia80 avg64 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring and external interconnection of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024