APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 10872 Issued:2004-03-12
Revised:2011-12-06
Style 10872 Single conductor with extruded insulation.

Rating105 deg C, 600 Vac, Cable flame, 75 deg C Wet, Sunlight Resistant.
ConductorNo. 18, 16, 12 AWG. Stranded.
InsulationExtruded PVC. Inner Insulation - 25 mils minimum average, 23 mils minimum at any point. Outer insulation - 31 mils minimum average thickness, 28 mils minimum at any point.
AssemblyBoth inner and outer insulation employing R/C QMTT2 Compound suitable for THW Wire Insulation and 720 Hrs. Sunlight Resistant.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial Interconnecting Cable, 75C Wet, Moisture Resistance and 720 hrs. Sunlight Resistance