|
Rating | 105 deg C, 600 Vac, Horizontal flame. |
|
Conductor | 44 AWG - 6 AWG, solid or stranded. |
|
Insulation | Extruded TPES, see Facing page for compound. |
| Conductor size AWG | Minimum average thickness mils | Minimum thickness at any point mils |
| 44-20 | 8 | 6.5 |
| 19-16 | 10 | 8.5 |
| 15-10 | 12 | 10 |
| 9-6 | 16 | 14 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring where not subject to mechanical abuse or movement. |
|