Rating | 80 deg C, 30 V, Cable flame. |
|
Conductor | 32 AWG - 12 AWG, solid or stranded. |
|
Insulation | Extruded TPE, 7 mils minimum average, 6 mils minimum at any point. |
|
Shield | Optional. |
|
Covering | Optional. |
|
Jacket | Extruded TPE thickness |
| Dia. of Assembly Under Jacket in Inches | Min average mils | Min at any point mils |
| 0.700 or less | 13 | 10 |
| 0.701 - 1.500 | 13 | 10 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External wiring in Class 2 circuit. |
|