APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11182 Issued:2009-02-04
Revised:2011-10-17
Style 11182 Single conductor cable using extruded non-integral jacket

Rating90 deg C, 600 V ac, 60 deg C Oil, Cable flame.
Conductor30 AWG - 4/0 AWG, solid or stranded round, tinned or bare copper.
InsulationExtruded TPE, 30 mils minimum average thickness, 27 mils minimum thickness at any point.
ShieldOptional.
CoveringOptional. Material other than TPE or PVC. A separator required in the case of no shield provided.
JacketExtruded PVC, 30 mils minimum average thickness, 24 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.