APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11212 Issued:2009-06-02
Revised:2011-10-20
Style 11212 Single conductor cable using non-integral jacket.

Rating80 deg C, 300 Vac, Cable flame.
InsulationLabeled or complying with manufacturer's AWM procedure having a minimum rating of 80 deg C, 300 Vac.
ShieldOptional.
CoveringOptional.
JacketmPPE-PE.
Diameter of core assembly under jacketMinimum averageMinimum at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024