APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11234 Issued:2009-10-30
Revised:2011-09-22
Style 11234 Single Conductor Cable with Extruded Non-Integral Jacket

Rating90 deg C, 600 Vac, Cable flame.
Conductor10 AWG - 500 kcmil, solid or stranded.
InsulationFRPE.
Conductor sizeMinimum averageMinimum at any point
10-5 AWG30 mils27 mils
4-2 AWG45 mils41 mils
1-2/0 AWG55 mils49 mils
3/0 AWG-250 kcmil60 mils54 mils
500 kcmil80 mils72 mils
JacketFRPE.
Diameter of core assembly under jacketMinimum averageMinimum at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal and external wiring.

UL and the UL Logo are trademarks of UL LLC © 2024