Rating | 90 deg C, 1000 Vac, Cable flame, Optional - Sunlight resistant. |
|
Conductor | 10 AWG - 500 kcmil, solid or stranded. |
|
Insulation | FRPE. |
| Conductor size | Minimum average | Minimum at any point |
| 10-5 AWG | 30 mils | 27 mils |
| 4-2 AWG | 45 mils | 41 mils |
| 1-2/0 AWG | 55 mils | 49 mils |
| 3/0 AWG-250 kcmil | 60 mils | 54 mils |
| 500 kcmil | 80 mils | 72 mils |
|
Shield | Optional. |
|
Jacket | FRPE. |
| Diameter of core assembly under jacket | Minimum average | Minimum at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal and external wiring. |
|