APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11244 Issued:2010-01-25
Revised:2012-05-29
Style 11244 Single conductor using non-integral jacket

Rating105 deg C, 30000 Vdc, Horizontal flame.
Conductor24 AWG - 10 AWG. solid or stranded round.
InsulationLabeled or complying with manufacturer's AWM procedure.
ShieldTinned copper.
JacketExtruded PVC, 34 mils minimum average thickness, 27 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.