APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11396 Issued:2012-01-12
Revised:New
Style 11396 Single conductor with non-integral jacket.

Rating80 deg C,30 V, Horizontal flame.
Conductor40 AWG - 10 AWG, solid or stranded.
InsulationExtruded PFA, 11 mils minimum average thickness, 10 mils minimum thickness at any point.
ShieldOptional. Inner and/or Outer.
JacketExtruded PVC, 30 mils minimum average thickness, 24 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.