Rating | 105 deg C, 1000 Vac, Horizontal flame. |
|
Conductor | 30 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Extruded PVC. |
| Conductor size | Minimum average thickness (mils) | Minimum thickness at any point (mils) |
| 30 - 10 AWG | 30 | 27 |
| 9 - 8 AWG | 45 | 41 |
| 7 - 2 AWG | 60 | 54 |
| 1 - 4/0 AWG | 80 | 72 |
| 250 - 500 kcmil | 95 | 86 |
| 501 - 1000 kcmil | 110 | 99 |
| 1001 - 2000 kcmil | 125 | 112 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring. |
|