Rating | 105 deg C, 2000 V ac and/or 2000 V dc, Horizontal flame. |
|
Conductor | 30 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Extruded PVC. |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 30 - 9 AWG | 30 mils | 27 mils |
| 8 - 7 AWG | 45 mils | 40 mils |
| 6 - 2 AWG | 60 mils | 54 mils |
| 1 - 4/0 AWG | 80 mils | 72 mils |
| 250 - 500 kcmil | 95 mils | 86 mils |
| 550 - 1000 kcmil | 110 mils | 99 mils |
| 1100 - 2000 kcmil | 125 mils | 112 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring. |
|