APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11675 Issued:2016-11-17
Revised:New
Style 11675 Single conductor with extruded insulation and extruded non-integral covering.

Rating90 deg C,600 Vac FT2 flame; Oil Res 60 (required); Moisture Res 60 (required).
Conductor22 AWG - 1000 kcmil, solid or stranded, tinned or bare copper.
InsulationExtruded PVC, QMTT2 compound suitable for THWN-2.
Conductor sizeMinimum average thicknessMinimum thickness at any poing
22-12 AWG15 mils13 mils
11-10 AWG20 mils18 mils
9-8 AWG30 mils27 mils
7-6 AWG30 mils27 mils
5-2 AWG40 mils36 mils
1-4/0 AWG50 mils45 mils
225-500 kcmil60 mils54 mils
501-1000 kcmil70 mils63 mils
CoveringExtruded Nylon Covering (Polyamide), QMTT2 compound minimum Oil I rating.
Conductor sizeMinimum thickness at any point
22-12 AWG4 mils
1110 AWG4 mils
9-8 AWG 5 mils
7-6 AWG5 mils
5-2 AWG6 mils
1-4/0 AWG7 mils
225-500 kcmil8 mils
501-1000 kcmil9 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial - Internal Wiring of Appliances with FT2 Flame Rating.