APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11704 Issued:2017-05-23
Revised:New
Style 11704 Single Conductor with Extruded Insulation

Rating80 deg C, 30 Vac.
Conductor50 AWG - 2000 kcmil, Solid or Stranded Round.
InsulationExtruded foamed PE
Conductor sizeMinimum average thicknessMinimum thickness at any point
50-10 AWG10 mils9 mils
9-8 AWG15 mils13 mils
7-2 AWG30 mils27 mils
1-4/0 AWG80 mils72 mils
251-500 kcmil95 mils86 mils
501-1000 kcmil110 mils99 mils
1001-2000 kcmil125 mils112 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseFor Further Processing into Cables.

UL and the UL Logo are trademarks of UL LLC © 2024