APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11719 Issued:2017-06-30
Revised:2017-07-06
Style 11719 Single Conductor with Extruded Insulation and Non-Integral Jacket

Rating90 deg C, 600 Vac, Cable flame; Oil Res 60 (required).
Conductor30 AWG - 4/0 AWG, solid or stranded.
InsulationExtruded TPU, 30 mils minimum average thickness, 27 mils minimum thickness at any point.
ShieldOptional
CoveringOptional
JacketExtruded TPU
AWG conductor SizeMinimum average thickness (mils)Minimum thickness at any point (mils)
30-93027
8-74540
7-26054
1-4/08072
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024