APPLIANCE WIRING MATERIAL
Subj.758
Section
1
Page
11760
Issued:
2018-08-16
Revised:
2018-08-20
Style
11760
Single Conductor with Extruded Insulation
Rating
105 deg C,600 Vac, Horizontal Flame Test, Optional IEC 60332-1, Optional IEC 60332-2
Conductor
30 AWG - 6 AWG, Solid or Stranded Round
Insulation
Extruded TPE
AWG Size
mils min average
mils min at any point
30-9
30
27
8-7
45
40
6
60
54
Standard
Appliance Wiring Material UL 758.
Marking
General.
Use
Internal Wiring.