APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11814 Issued:2019-05-31
Revised:New
Style 11814 Single Conductor with Extruded Insulation

Rating200 deg C, 1000 Vac, Horizontal flame.
Conductor32 AWG - 4 AWG, solid or stranded..
InsulationExtruded ETFE
Conductor sizeAverage insulation thicknessMinimum thickness at any point
32-15 AWG8 mils7.5 mils
14-13 AWG10 mils9 mils
12-11 AWG12 mils10 mils
10-9 AWG14 mils12 min
8-7 AWG16 mils14 mils
6-4 AWG18 mils16 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.