Rating | 60 deg C, 120 Vac, Horizontal flame. |
|
Insulation | Labelled 14 AWG or 12 AWG, solid, same as for Type TW wire. The insulation shall be yellow in color to indicate 120 volt rating. |
|
Paper Wrap | Formed of four pieces of moisture resistant crepe type Kraft paper, 1 by 0.005 inches, or 1-1/2 by 0.003 inches, applied in a manner as to provide 5 thickness of paper over the Labelled same as for Type TW conductor with an approximate 3/16 inhes overlap between pieces. |
|
Covering | Glass or combination Cotton-Glass braid saturated with a flame-retardant and moisture-resistant impregnant. |
|
Over-All Finish | Optional. The outer covering may be finished with an aluminum paint or white paint. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Only as factory assembled Non-Heating Leads on Radiant Heating Cable Units. |
|