Rating | 105 deg C, 600 Vac and/or 750 Vdc, Horizontal flame. |
|
Conductor | 44 AWG - 2000 kcmil, solid or stranded. |
|
Insulation | Extruded PVC |
| Conductor size | Minimum average thickness | Minimum thickness at any point |
| 44-9 AWG | 28 mils | 25 mils |
| 8-7 AWG | 42 mils | 37 mils |
| 6-2 AWG | 49 mils | 44 mils |
| 1-4/0 AWG | 63 mils | 56 mils |
| 250-500 kcmil | 77 mils | 69 mils |
| 550-1000 kcmil | 92 mils | 82 mils |
| 1100-2000 kcmil | 105 mils | 94 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal Wiring. |
|