APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11821 Issued:2019-08-19
Revised:New
Style 11821 Single conductor with extruded insulation.

Rating105 deg C, 600 Vac and/or 750 Vdc, Horizontal flame, 60 deg C Oil.
Conductor44 AWG - 2000 kcmil, solid or stranded.
InsulationExtruded PVC
Conductor sizeMinimum average thicknessMinimum thickness at any point
44-9 AWG28 mils25 mils
8-7 AWG42 mils37 mils
6-2 AWG49 mils44 mils
1-4/0 AWG63 mils56 mils
250-500 kcmil77 mils69 mils
550-1000 kcmil92 mils82 mils
1100-2000 kcmil105 mils94 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024