APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11831 Issued:2019-10-11
Revised:2019-10-03
Style 11831 Single conductor with extruded insulation

Rating90 deg C,600 Vac flame; Sunlight Res (optional).
Conductor30 AWG - 1000 kcmil, solid or stranded.
InsulationExtruded PVC;
Conductor SizeMinimum Average Thickness (mils)Minimum Thickness at Any Point (mils)
30-12 AWG1513
11-10 AWG2018
9-5 AWG3027
4-2 AWG4036
1-4/0 AWG5045
213-500 kcmil6054
501-1000 kcmil7063
CoveringOptional. Extruded Nylon covering with a minimum average thickness of 4 mils.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring or for further processing into cables.

UL and the UL Logo are trademarks of UL LLC © 2024