APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 11870 Issued:2020-07-02
Revised:New
Style 11870 Single Conductor with Extruded Insulation

Rating80 deg C, 300 Vac.
Conductor32 AWG - 2000 kcmil, solid or stranded round, tinned or bare copper.
InsulationExtruded PP
AWG sizemils min averagemils min at any point
36-20 AWG1210
19-16 AWG1412
15-10 AWG1614
9-6 AWG2219
5-2 AWG2825
1-4/0 AWG3330
250-500 kcmil4540
501-1000 kcmil6054
1001-2000 kcmil8072
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseFor Further Processing into Cables for Electronic Equipment of Appliances.