APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 12077 Issued:2023-11-08
Revised:2023-11-14
Style 12077 Single Conductor with Extruded Insulation.

Rating105 deg C, 300 Vac, Horizontal Flame
Conductor40 AWG - 2000 kcmil, solid or stranded.
InsulationExtruded PVC non-separable dual layered insulation with inner layer of 7 mils minimum average thickness and 6 mils minimum thickness at any point, outer layer of 6 mils minimum average thickness and 5 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.