APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 12095 Issued:2024-04-02
Revised:New
Style 12095 Single-conductor cable using non-integral jacket.

Rating80 deg C,300 Vac, Cable flame.
Conductor50 AWG - 2000 kcmil, stranded.
InsulationExtruded FEP, 15 mils minimum average thickness, 13 mils minimum thickness at any point.
CoveringExtruded FRPE over insulation.
ShieldRequired.
JacketExtruded TPU
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less40 mils32 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or External Wiring.