APPLIANCE WIRING MATERIAL
Subj.758 Section 1 Page 1278 Issued:1961-06-26
Revised:2013-01-10
Style 1278 Single conductor with extruded insulation

Rating80 deg C, 600 Vac, Horizontal flame, 60 deg C Wet. Optional - 60 deg C or 80 deg C Oil.
Conductor4 AWG - 4/0 AWG, stranded.
InsulationExtruded PVC, 80 mils minimum average thickness, 72 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024